For small volumes, a manual injection gun may be used; for larger volumes, a pump should be used. The pressure used for injection must be carefully selected based on grout properties, crack characteristics, and structural integrity of the medium to be grouted
A pressure of 2-3 kg shall be maintained during grouting.
If the crack is vertical, the injection process should begin with pumping grout into the entry port at the lowest elevation until the grout level reaches the entry port above. The lower injection port is then capped, and the process is repeated at successively higher ports until all the nozzles are grouted and capped.
For horizontal cracks, injection should proceed from one end of the crack to the other in the same manner.
If the pressure cannot be maintained, the grout will flow into the unfilled portions or will leak out of the crack.
After the grout has set completely, the extra length of the nozzle shall be cut or removed from the surface.
Filling Honeycombing / Voids in concrete
The same grout mixture shall be used for this purpose. The injection ports should be fixed on the entire area to be grouted in a staggered manner at distance of 500 mm c/c. Fixing or as directed by the concerned engineer, sealing and grouting of injection ports shall be carried out as per the application methodology given above.
|